While the DSE5110 is not a full synchronizer like the DSE7320, it does support simple parallel load sharing with other DSE5110 modules using a load share line (droop mode). The software allows you to adjust the droop percentage and the kW load share balance.
| Problem | Software Diagnostic | Solution | | :--- | :--- | :--- | | | Check "Engine Interface" – Is the fuel output active? Check RPM reading. | Adjust "Crank Disconnect" frequency or change fuel solenoid logic. | | Generator breaker won't close | Look at "Protections" tab – Is a voltage or frequency alarm active? | Increase "Mains Close Delay" or check generator AVR settings. | | False low oil pressure alarm | View "Analogue Inputs" – Is the sender reading 0 ohms with engine off? | Change sender curve or adjust "Oil Pressure Warning Delay" timer. | | Module powers off when cranking | Check battery voltage during cranking in "Real-Time Data". | Battery voltage dropping below 8V (for 12V systems) will reset the module. |
The DSE5110 is highly customizable via its expandable I/O.