Siemens Sinamics V20 Quick - Start Guide

0.12 kW to 3.0 kW (0.16 hp to 4.0 hp)

| Fault Code | Cause | Immediate Fix | | --- | --- | --- | | F0001 | Overcurrent | Increase ramp time, check motor cable | | F0002 | Overvoltage | Check braking resistor or extend decel ramp | | F0003 | Undervoltage | Check supply voltage, power loss | | F0004 | I²t motor overtemperature | Reduce load, check P0305 motor current | | A0501 | No motor data | Run quick commissioning first | siemens sinamics v20 quick start guide

Locate the input terminals. On most Frame A and B units, these are the top terminals labeled . siemens sinamics v20 quick start guide